Maximum output: | 110dB(A) @ 1 metre [101dB(A) @ 10ft/3m] Class II version: 94dB(A) @ 1 metre [85dB(A) @ 10ft/3m] |
Nominal output: | 105dB(A) @ 1m +/- 3dB – Tone 4 [96dB(A) @ 10ft/3m] Class II version: 90dB(A) @ 1 metre [81dB(A) @ 10ft/3m] |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Full range |
Effective range: | 125m/410ft @ 1KHz |
Voltages DC: | 24Vdc (11.5-54Vdc) |
Voltages AC: | 230Vac (100-240Vac) |
In-rush: | 815mA within 4ms @ 24Vdc |
Stage switching: | DC units: positive or negative AC units: common supply line |
Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
Ingress protection: | EN60529: IP66/67 UL50E / NEMA250: 4 / 4X / 3R / 13 |
Enclosure material: | Marine grade LM6 aluminium alloy |
Enclosure colour: | Red or Grey, custom colours available on request |
Enclosure finish: | Chromate & powder coated finish |
Cable entries: | 1×1/2"NPT & 2xM20 Thread adaptors available |
Stopping plugs: | Brass, Nickel Plated or Stainless Steel |
Terminals: | 0.5 – 2.5mm² (20-14AWG) – 12AWG solid core conductor Pluggable & duplicated terminals |
Line monitoring: | Blocking diode included EOL Min. 500 Ohm 2W, or 3k3 Ohm 0.5W resistor or diode (DC versions) can be fitted |
Ground/Earth stud: | M5 |
Enclosure volume: | <2 litres |
Installation temp: | -55 to +85°C [-67° to +185°F] |
Storage temp: | -55 to +85°C [-67° to +185°F] |
Relative humidity: | 99% |
Vibration test: | 35Hz for a duration 4Hr (UL464) |
Jarring test: | 3ft/lb Energy (UL464) |
Impact test: | 3x 5lb (UL464) |
MTBF DC: | 225.16 years / 1,972,386 hours – MIL 217 |
MTBF AC: | 138.96 years / 1,217,285 hours – MIL 217 |
Weight: | 4.00kg/8.80lbs |
Nominal Voltage: |
Voltage range: |
Nominal current: |
Max. current: |
In-rush: |
---|---|---|---|---|
12Vdc | 11.5-54Vdc | 221mA | 221mA | - |
24Vdc | 11.5-54Vdc | 185mA | 221mA | 815mA <4ms |
48Vdc | 11.5-54Vdc | 115mA | 221mA | - |
115Vac 50/60Hz | 100-260V ac | 73mA | 80mA | - |
230Vac 50/60Hz | 100-260V ac | 48mA | 80mA | - |
Part Code: | Identifier: | Description: |
---|---|---|
Product type: | D1xS1 | D1xS1 alarm horn sounder |
Horn type: | R | Radial omni-directional horn |
Voltage: | DC024 AC230 |
11.5-54Vdc 100-240Vac |
Cable entries:[e] | A B C D F G Note: |
2 x M20x1.5mm & 1 × 1/2"NPT 2 × 1/2"NPT – adaptors 2 × 3/4"NPT – adaptors 2 x M25x1.5mm – adaptors 1 × 3/4"NPT – adaptor 1 x M25x1.5mm – adaptor All entries, excluding thread adaptors, supplied with stopping plugs installed. |
Stopping plug/ adaptor material: [m] |
B N S |
Brass Nickel plated brass Stainless steel |
Bracket material: [s] | 1 3 5 |
A4 316 Stainless Steel A4 316 St/St with Equip. Tag A4 316 St/St with Equip. Tag and Duty Label |
Product version: [v] | A D S T |
UL, cUL, ULC, IECEx, ATEX, PESO, CSFM, INMETRO – SIL1 & SIL2 Route 2H Class II – UL, cUL UL, cUL, ULC, IECEx, ATEX, PESO, CSFM – SIL2 Route 1H with diagnostics SFF: >99% IECEx, ATEX, PESO, INMETRO – Telephone/Relay initiate |
Product option: [o] |
1 Z X Y K V |
Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 Stage control Config. 5 (DC) and Config. 2 (AC) Stage control Config. 6 |
Enclosure colour: [x] | R G S |
Red Grey Special colour – contact E2S |
Accessories: | ||
SP65-0001-A4 SP65-0003-A4 |
Pole Mount Bracket Kit St/St A4 (316) Sunshade – St/St A4 (316) |
Alarm stage control: | ||
---|---|---|
Please review the installation manual and wiring schematics for remote stage control and EOL resistor monitoring configuration options: | ||
Config. 1 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 2 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 3 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | |
Config. 4 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | |
Config. 5 [DC]: | Product option ‘K’. Horn continuously powered. Voltage free activation of up to 3 alarm stages | |
Config. 6 [DC]: | Product option ‘V’. Independent activation of up to 4 Alarm Stages with EOL on all stages. Forward polarity monitoring | |
Config. 1 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts | |
Config. 2 [AC]: | Product option ‘K’. Horn continuously powered. Voltage free activation of up to 3 alarm stages |