Sound level outputs are up to 117dB(A) at 1 metre with a choice of 32 alarm tones and 3 remotely selectable stages.
The BEx range features enclosures manufactured from corrosion proof, marine grade copper free LM6 aluminium which is phosphated and powder coated.
The re-entrant flare horns are high impact, fire retardant ABS. All models have two M20 cable entries, large termination areas
containing in & out terminals (Ex de version only) and an ingress protection of IP66/67 (Ex d) and IP66 (Ex de).
For fire applications the BExS110D 24V dc siren is CPD EN89/106/EEC compliant (EN54-3 tested).
Maximum output: | 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m] |
Nominal output: | 110dB(A) @ 1m +/- 3dB – Tone 2 [101dB(A) @ 10ft/3m] |
No. of tones: | 32 (UKOOA / PFEER compliant) |
No. of stages: | 3 |
Volume control: | Max. 110dB(A); Min. 72dB(A) – Tone 2 |
Effective range: | 100m @ 1KHz |
Voltages DC: | 12vdc; 24vdc; 48vdc |
Voltages AC: | 115vac; 230vac |
Stage switching: | Negative or positive |
Ingress protection: | S110D : IP66/67 S110E : IP66 |
Enclosure matl: | Marine grade copper free LM6 Aluminium |
Enclosure finish: | Chromate & powder coated finish – anti-corrosion. |
Colour: | RAL3000 Red (others available on request) |
BExS110 flare: | High impact UL94 V0 & 5VA FR ABS (Red) |
BExDS110 flare: | Anti-Static High impact ABS (Black) |
Cable entries: | Dual M20 ISO (one stopping plug inc) |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
Enclosure volume: | <2 litres |
Line monitoring: | Blocking diode included EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor or diode (DC versions) can be fitted |
Weight: | DC: 3.00kg AC: 3.20kg |
*SPL data +/-3dB(A). Measured at optimum voltage. |
Version: | Voltage: | Current: | |
---|---|---|---|
12V dc | +/-25% | 195mA | |
24V dc | +/-25% | 265mA | |
48V dc | +/-25% | 130mA | |
115V ac | 50/60Hz | +10/-10% | 110mA |
230V ac | 50/60Hz | +10/-10% | 56mA |
Part Code: | Classification: |
---|---|
BExS110D** | ATEX / IECEx: II 2G Ex d IIB T4 Ta. -50°C to +70°C II 2G Ex d IIC T4 Ta. -50°C to +55°C |
GOST-R: 1ExdIICT4 Ta. -50° to +55°C |
|
BExS110E** | ATEX / IECEx: II 2G Ex de IIB T4 Ta. -50°C to +70°C II 2G Ex de IIC T4 Ta. -50°C to +55°C |
GOST-R: 2ExdeIICT4 Ta. -50° to +55°C |
|
BExDS110D** | ATEX / IECEx: II 2G Ex d IIB T4 Ta. -50° to +70°C II 2G Ex d IIC T4 Ta. -50° to +55°C II 2D Ex tD A21 IP67 T115 based on max.Ta 70°C |
GOST-R: 1ExdIICT4 Ta. -50° to +55°C T100°C DIP A21 Ta T4 |
|
BExDS110E** | ATEX / IECEx: II 2G Ex de IIB T4 Ta. -50° to +70°C II 2G Ex de IIC T4 Ta. -50° to +55°C II 2D Ex tD A21 IP66 T115 based on a max. Ta. of 70°C |
GOST-R: 2ExdeIICT4 Ta. -50° to +55°C DIP A21 Ta T4 |
|
** = Voltage reference: | |
Voltage options: | 12DC, 24DC, 48DC, 115AC, 230AC |
Add ‘-P’ to part number for Programmable version Add ‘-M’ to part number for MED approved version (24V dc only) |