Datasheet | Datasheet.pdf |
Installation Manual | D118-01-501-IS_Issue_1__AB112STR_.pdf |
Russian EAC Declaration of Conformity | D-GB.GA05.B.12595-20-24.03.2025.pdf |
Russian Maritime register | 19.00193.278.pdf |
Declaration of Conformity | DC-027_Issue_F_Spectralarm.pdf |
2D drawing (PDF) | D118-05-501_Issue_1.pdf |
2D drawing (DWG) | D118-05-501_Issue_1.DWG |
3D drawing (STEP) | D118-05-501-3D_Issue_A.STEP |
Wiring Schematic | D118-06-501_Issue_1.pdf |
Alarm Horn: | |
---|---|
Maximum output: | High power level: 120dB(A) @ 1 m ±3dB [111dB(A) @ 10ft/3m ±3dB] Default power level: 117dB(A) @ 1 m ±3dB [108dB(A) @ 10ft/3m ±3dB] |
Nominal output: | High power level: 118dB(A) @ 1m ±3dB [109dB(A) @ 10ft/3m ±3dB] Default power level: 114dB(A) @ 1m ±3dB [105dB(A) @ 10ft/3m ±3dB] |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Full range to 0dB(A) |
Effective range: | High power level: 214m/702ft @ 1KHz Default power level: 153m/502ft @ 1KHz |
In rush: | 815mA within 4.0ms @ 24Vdc |
Stage switching: | Negative (common positive) |
Xenon Beacon: | |
Energy: | 5 Joules (5Ws) |
Flash rate: | 1Hz (60 fpm) DC units: Optionally 1.5Hz & double strike |
Synchronisation: | 1Hz flash rate automatically synchronised |
Peak Candela: | 500,000 cd – calculated from energy (J) |
Effective Intensity cd: | 250 cd – calculated from energy (J) |
Peak Candela: | 49,788 cd* – measured ref. to I.E.S. |
Effective Intensity cd: | 125 cd* – measured ref. to I.E.S. |
Lens colours: | Amber, Blue, Clear, Green, Red & Yellow |
Tube life: | Emissions are reduced to 70% after 5 million flashes |
General: | |
Ingress protection: | IP65 |
Enclosure: | High impact UL94 V0 & 5VA FR ABS/PC |
Lens colour filter: | Field replaceable UV stable PC |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
Line monitoring: | Diode polarized for use in supervised circuits |
Operating: | -40 to +66°C [-40° to +151°F] |
Storage: | -40 to +70°C [-40° to +158°F] |
Relative humidity: | 95% at 20°C [68°F] |
Weight DC: | 2.00kg / 4.40Ibs |
Weight AC: | 2.30kg / 5.06Ibs |
Product Version: | Nominal Voltage: | Voltage Range: | Beacon Current: | Horn Default Power Level Current: |
Horn High Power Level Current: |
---|---|---|---|---|---|
DC012 | 12Vdc | 10-14Vdc | 600mA | 280mA | 376mA |
DC024 | 24Vdc | 20-28Vdc | 300mA | 225mA | 430mA |
DC048 | 48Vdc | 42-54Vdc | 250mA | 122mA | 223mA |
AC115 | 115Vac | 103.5-126.5Vac 50/60Hz | 70mA | 100mA | 173mA |
AC230 | 230Vac | 207-253Vac 50/60Hz | 35mA | 64mA | 105mA |
Variable: | Identifier: | Description: |
---|---|---|
Product type: | AB112STR | Combined alarm horn sounder & Xenon strobe |
Voltage: | DC012 DC024 DC048 AC115 AC230 |
12Vdc (10-15Vdc) 24Vdc (20-28Vdc) 48Vdc (42-54Vdc) 115Vac 50/60Hz 230Vac 50/60Hz |
Back box/cable entries: [e] | A | Back box with mounting lugs – 2 x M20, 1/2"NPT clearance |
Stopping plug material: [m] | A | ABS |
Equip. tag/Duty label: [s] | 0 1 2 |
No equip. tag or Duty label 316 (A4) St/St Equip. tag/Duty label Metalised Polyester Equip. tag/Duty label |
Product version: [v] |
A | RMRS, EAC, CE, UKCA |
Product option: [o] |
1 Z X Y |
Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 or 8 |
Enclosure colour: [x] | G R S |
Grey Red Special colour – contact E2S |
Lens colour: [y] | A B C G M R Y |
Amber Blue Clear Green Magenta Red Yellow |
Alarm stage control: | ||
Please review the installation manual and wiring schematics for remote stage control and EOL resistor monitoring configuration options: | ||
Config. 1 or 5 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 2 or 6 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 3 or 7 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | |
Config. 4 or 8 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | |
Config. 9 or 10 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts |