D2xC1X05 Alarm Horn Sounder & Xenon Strobe 5J 1-34-020

Product Image
Product Image
Product Image
The D2xC1X05 features a high output, 116dB(A) alarm horn sounder combined with a 5 Joule Xenon strobe warning light / beacon. Globally approved, the robust Type 4/4X, IP66 enclosure ensures suitability for all haz loc fire alarm and general signalling applications.
Request a quote for this product
Voltage
Cable entries
Stopping plug/adaptor material
Guard Material
Product version
Product option
Enclosure colour
Lens colour
Part Number:
D2xC1X05
Request Price or enquire about this product
Enquire about
Alarm Horn Sounder & Xenon Strobe 5J

Description

The corrosion proof, marine grade aluminium die cast enclosure is chromated and powder coated providing resilience in the harshest of hazardous location environments. One device, globally certified: ATEX, IECEx Zone 2 & 22; NEC/CEC CI D2 and CII D2; NEC CI Zone 2 and Zone 22; CEC Zone 2 & 22 and CII D2. UL & cUL approved 24Vdc version for fire alarm use.

Downloads

Datasheet Datasheet.pdf
Installation Manual D189-01-501-IS_Issue_3__D2xC1X05_X10_.pdf
IECEx certificate IECEx_ULD_14.0004X_007_D2x.pdf
ATEX certificate DEMKO_14_ATEX_4786493904X_Rev7_D2x.pdf
UL certificate of compliance UL_CoC_-_20140624-E230764_Vol.1_Sec.2_D2xS_C1_L.pdf
CSFM Listing CSFM_Listing_2279-0503_D2xS_2025.pdf
UKCA Certificate UL21UKEX2131X_Rev._1_D2x.pdf
Russian Ex certificate C_RU_C-GB.71..00273_20.pdf
ECAS Ex Approval 24-07-117232_E24-07-120613_NB0007_D2x.pdf
Declaration of Conformity DC-061_Issue_K_D2x.pdf
Declaration of Conformity UKCA DC-102_Issue_B_D2x_UKCA.pdf
2D drawing (PDF) D189-05-501_Issue_B.pdf
2D drawing (DWG) D189-05-501_Issue_A.dwg
3D drawing (STEP) D189-05-501-3D_Issue_1.STEP
Wiring Schematic D189-06-501_Issue_B.pdf
Nameplate Drawing D189-09-501_Issue_1.pdf
Equipment Tag Drawing D254-00-131_Issue_1.pdf
Duty Label Drawing D254-00-051_Issue_1.pdf
Pole Mount & Sun Shade Drawing D217-05-641_Issue_1__D2xC1_.pdf
Hi-res product image 1 (TIFF) 1-34-020_D2xC1X05_R4.tif
Hi-res product image 2 (TIFF) 1-34-020_D2xC1X05_R2.tif
Hi-res product image 3 (TIFF) 1-34-020_D2xC1X05_G4.tif

Features

  • 5 Joule Xenon beacon with 116dB(A) alarm horn
  • UL464/UL1638 Fire Alarm
  • Effective Intensity: 94.78 cd
  • Peak Candela: 33,410 cd
  • 64 alarm tones, 4 remotely selectable alarm stages/channels
  • Field replaceable lens colour filters
  • Dual cable entries
  • Supplied with haz loc rated stopping plugs/adaptors

Specification

Alarm Horn Sounder:
Maximum output: 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
Nominal output: 112dB(A) @ 1m +/- 3dB – Tone 2 [103dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A) [Tone 2]
Effective range: 125m/410ft @ 1KHz
Stage switching: DC units – Positive or Negative line.
AC units – common supply line
Xenon Strobe Beacon:
Energy: 5 Joules (5Ws)
Flash rate: 1Hz (60 fpm)
Peak Candela: 500,000 cd – calculated from energy (J)
Effective Intensity cd: 250 cd – calculated from energy (J)
Peak Candela: 33,410 cd – measured ref. to I.E.S.
Effective Intensity: 94.78 cd – measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green, Magenta, Red & Yellow
Tube life: Emissions are reduced to 70% after 8 million flashes
General:
Voltages DC: 24V dc [20-28Vdc]; 48V dc [38-58Vdc]
In rush: 2.2A for <9ms
Voltages AC: 115V ac 50/60Hz; 230V ac 50/60Hz
Ingress protection: EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure material: Marine grade aluminium Al Si12 Cu
Enclosure colour: Red or Grey, custom colours available on request
Cable entries: 2 x M20 x 1.5mm threaded gland entries
Adaptors available to 1/2"NPT, 3/4"NPT and M25
Terminals: 0.5 – 2.5mm² (20-14 AWG)
Grounding stud: M5
Operating temp: -40 to +70°C [-40° to +158°F] – Class I Div 2
-40 to +50°C [-40° to +122°F] – All other approvals
Relative humidity: 95%
Weight: DC: 2.80kg/6.16Ibs AC:3.10kg/6.82Ibs

Current Consumption

Product Version: Nominal Voltage: Voltage Range: Current Consumption:
Alarm Horn Sounder:
DC024 24V dc 10-30V dc 313mA [at nominal voltage]
DC048 48V dc 38-58V dc 181mA [at nominal voltage]
AC115 115V ac 50/60Hz +/-10% 89mA
AC230 230V ac 50/60Hz +/-10% 52mA
Xenon Strobe Beacon:
DC024 24V dc 20-28V dc 275mA [at nominal voltage]
DC048 48V dc 42-54V dc 145mA [at nominal voltage]
AC115 115V ac 50/60Hz +/-10% 80mA
AC230 230V ac 50/60Hz +/-10% 30mA
Combined Horn & Strobe:
DC024 24V dc 20-28V dc 513mA [at nominal voltage]
DC048 48V dc 42-54V dc 311mA [at nominal voltage]
AC115 115V ac 50/60Hz +/-10% 174mA
AC230 230V ac 50/60Hz +/-10% 63mA

Part Codes

Part Code: Identifier: Description:
Product type: D2xC1X05 Haz Loc alarm horn sounder & Xenon strobe warning light / beacon
Voltage: DC024
DC048
AC115
AC230
24V dc – UL/cUL Fire Alarm
48V dc
115V ac
230V ac
Cable Entry Type:[e] A
B
C
D
E
F
G
2 x M20x1.5mm
2 × 1/2" NPT – adaptors
2 × 3/4" NPT – adaptors
2 x M25x1.5mm – adaptors
1 × 1/2" NPT – adaptor
1 × 3/4" NPT – adaptor
1 x M25x1.5mm – adaptor
Stopping plug/
adaptor material: [m]
N
S
Nickel Plated
Stainless Steel
Guard material & tag: [s] 1
3
5
A4 316 Stainless Steel
A4 316 St/St with Equip. Tag
A4 316 St/St with Equip. Tag & Duty Label
Product version: [v] A UL, cUL, IECEx, ATEX, CSFM, Ex EAC
Product option:
[o]
1
T
X
Standard product
Tropicalisation
Custom configuration – contact E2S
Enclosure colour: [x] R
G
S
Red
Grey
Special colour – contact E2S
Lens colour: [y] A
B
C
G
M
R
Y
Amber
Blue
Clear
Green
Magenta
Red
Yellow
Accessories:
SP65-0001-A4
SP65-0003-A4
Pole Mount Bracket Kit St/St A4 (316)
Sunshade – St/St A4 (316)

Approvals

  • UL File ref: E230764
  • IECEx cert: IECEx ULD 14.0004X
  • ATEX cert: DEMKO 14 ATEX 4786493904X
  • CSFM listing: 7136-2279:0503
  • Ex EAC certified: EAC RU C GB.AA71.B.00273/20

Coding

  • NEC / CEC:
    Class I Div 2 ABCD T2B Ta -40°C to +70°C
    Class I Div 2 ABCD T2C Ta -40°C to +55°C
    Class I Div 2 ABCD T2D Ta -40°C to +40°C
    Class II Div 2 FG T5 Ta -40°C to +50°C
    Class III Div 1&2 Ta -40°C to +50°C
  • NEC:
    Class I Zone 2 AEx ec IIC T2 Gc Ta -40ºC to +50°C
    Zone 22 AEx tc IIIC T120°C Dc Ta -40ºC to +50°C
  • CEC:
    Class I Zone 2 Ex ec IIC T2B Gc X Ta -40ºC to +50°C
    Class I Zone 2 Ex ec IIC T2C Gc X Ta -40ºC to +45°C
    Zone 22 Ex tc IIIC T120°C Dc Ta -40ºC to +50°C
  • IECEx & ATEX:
    II 3G Ex ec IIC T2 Gc Ta -40ºC to +50°C
    II 3D Ex tc IIIC T90ºC Dc Ta -40ºC to +50°C
    See product manual for full voltage specific coding.

Effective Candela lens colour factor

Amber Blue Clear Green Magenta Red Yellow
0.59 0.27 1.00 0.51 0.34 0.15 0.85

Tone Table

Stage 1 WAV file Frequency Description. Stage 2 Stage 3 Stage 4
T 1 /system/1/assets/files/000/000/405/405/214ccf82a/original/TF037.WAV 1000 Continuous – PFEER Toxic Gas T 3 T 2 T 44
T 2 /system/1/assets/files/000/000/386/386/ceb4e488c/original/TF009.WAV 1200/500 @ 1Hz Sweeping – DIN / PFEER P.T.A.P. T 1 T 3 T 44
T 3 /system/1/assets/files/000/000/412/412/fa8b418f9/original/TF045.WAV 1000 @ 0.5Hz (1s on, 1s off) Intermittent – PFEER Gen. Alarm T 1 T 2 T 44
T 4 /system/1/assets/files/000/000/383/383/11797b764/original/TF019.WAV 1.4KH-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s – NF C 48-265 T 44 T 24 T 1
T 5 /system/1/assets/files/000/000/382/382/2c2978b6a/original/TF017.WAV 544(100mS)/440 (400mS) – NF S 32-001 T 52 T 19 T 1
T 6 /system/1/assets/files/000/000/947/947/8f040484a/original/TF053.wav 1500/500 – (0.5s on , 0.5s off) x3 + 1s gap – AS4428 T 7 T 44 T 1
T 7 /system/1/assets/files/000/000/944/944/890010fd0/original/TF054.wav 500-1500Hz Sweeping 2 sec on 1 sec off – AS4428 T 6 T 44 T 1
T 8 /system/1/assets/files/000/000/417/417/abf396de0/original/TF003.WAV 500/1200Hz @ 0.26Hz(3.3s on, 0.5s off) – NEN 2575 T 44 T 24 T 35
T 9 /system/1/assets/files/000/000/953/953/5deedc543/original/TF055.wav 1000 (1s on, 1s off)x7 + (7s on, 1s off) – IMO Code 1a T 18 T 34 T 1
T 10 /system/1/assets/files/000/000/952/952/3a041fde3/original/TF056.wav 1000 (1s on, 1s off)x7 + (7s on, 1s off) – IMO Code 1a T 21 T 34 T 1
T 11 /system/1/assets/files/000/000/946/946/761de34c6/original/TF057.wav 420(0.5s on, 0.5s off)x3 + 1s gap – ISO 8201 Temporal T 44 T 1 T 8
T 12 /system/1/assets/files/000/000/945/945/689d9405a/original/TF058.wav 1000(0.5s on, 0.5s off)x3 + 1s gap – ISO 8201 Temporal T 44 T 1 T 8
T 13 /system/1/assets/files/000/000/950/950/2d337d14e/original/TF059.wav 422/775 – (0.85 on, 0.5 off) x3 + 1s gap – NFPA Temporal T 44 T 1 T 8
T 14 /system/1/assets/files/000/000/399/399/84b54dafb/original/TF034.WAV 1000/2000 @ 1Hz – Singapore T 23 T 3 T 35
T 15 /system/1/assets/files/000/000/393/393/744c6f53f/original/TF030.WAV 300 Continuous T 44 T 24 T 35
T 16 /system/1/assets/files/000/000/391/391/5f7a58b54/original/TF028.WAV 440 Continuous T 44 T 24 T 35
T 17 /system/1/assets/files/000/000/948/948/c697b364a/original/TF060.wav 470 Continuous T 44 T 24 T 35
T 18 /system/1/assets/files/000/000/949/949/7e429e658/original/TF061.wav 500 Continuous – IMO code 2 (Low) T 44 T 24 T 35
T 19 /system/1/assets/files/000/000/390/390/10abe0caa/original/TF027.WAV 554 Continuous T 64 T 24 T 35
T 20 /system/1/assets/files/000/000/384/384/5c30f9f4d/original/TF020.WAV 660 Continuous T 44 T 24 T 35
T 21 /system/1/assets/files/000/000/380/380/06feaa7b3/original/TF015.WAV 800 Continuous – IMO code 2 (High) T 44 T 24 T 35
T 22 /system/1/assets/files/000/000/406/406/49b88184e/original/TF043.WAV 1200 Continuous T 44 T 24 T 35
T 23 /system/1/assets/files/000/000/407/407/ecce63f4f/original/TF038.WAV 2000 Continuous T 15 T 3 T 35
T 24 /system/1/assets/files/000/000/421/421/b578af8a9/original/TF005.WAV 2400 Continuous T 48 T 20 T 35
T 25 /system/1/assets/files/000/000/951/951/d9ce2b2c6/original/TF062.wav 440 @ 0.83Hz (0.60s on, 0.60s off) Intermittent T 1 T 44 T 8
T 26 /system/1/assets/files/000/000/954/954/b703d99f1/original/TF063.wav 470 @ 0.9Hz (0.55s on, 0.55s off) Intermittent T 1 T 44 T 8
T 27 /system/1/assets/files/000/000/955/955/0f602886a/original/TF064.wav 470 @ 5Hz (0.10s on, 0.10s off) Intermittent T 1 T 44 T 8
T 28 /system/1/assets/files/000/000/956/956/dbb5f64db/original/TF065.wav 544 @ 1.14Hz (0.43s on, 0.44s off) Intermittent T 44 T 24 T 8
T 29 /system/1/assets/files/000/000/957/957/7bd3d8c1c/original/TF066.wav 655 @ 0.875Hz (0.57s on, 0.57s off) Intermittent T 1 T 44 T 8
T 30 /system/1/assets/files/000/000/397/397/d6d84d0c3/original/TF018.WAV 660 @ 0.28Hz (1.80s on, 1.80s off) Intermittent T 44 T 24 T 8
T 31 /system/1/assets/files/000/000/381/381/93f51c79a/original/TF016.WAV 660 @ 3.3Hz (0.15s on, 0.15s off) Intermittent T 30 T 24 T 8
T 32 /system/1/assets/files/000/000/410/410/a0f0ba2a6/original/TF033.WAV 745 @ 1Hz (0.50s on, 0.50s off) Intermittent T 44 T 24 T 8
T 33 /system/1/assets/files/000/000/379/379/51c1bb5a9/original/TF014.WAV 800 (0.25s on, 1.00s off) Intermittent T 53 T 24 T 8
T 34 /system/1/assets/files/000/000/388/388/b4cf9203e/original/TF023.WAV 800 @ 2Hz (0.25s on, 0.25s off) – IMO code 3.a (High) T 56 T 24 T 8
T 35 /system/1/assets/files/000/000/377/377/ac5498db0/original/TF011.WAV 1000 @ 1Hz (0.50s on, 0.50s off) Intermittent T 44 T 24 T 8
T 36 /system/1/assets/files/000/000/378/378/6380218ec/original/TF013.WAV 2400 @ 1Hz (0.50s on, 0.50s off) Intermittent T 21 T 24 T 8
T 37 /system/1/assets/files/000/000/958/958/a90e62da4/original/TF067.wav 2900 @ 5Hz (0.10s on, 0.10s off) Intermittent T 53 T 24 T 8
T 38 /system/1/assets/files/000/000/959/959/f34b52faa/original/TF068.wav 363/518 @ 1Hz (0.50s / 0.50s) Alternating T 1 T 8 T 19
T 39 /system/1/assets/files/000/000/960/960/368703340/original/TF069.wav 450/500 @ 2Hz (0.25s / 0.25s) Alternating T 1 T 8 T 19
T 40 /system/1/assets/files/000/000/385/385/a85a0a356/original/TF021.WAV 554/440 @ 1Hz (0.50s / 0.50s) Alternating T 44 T 24 T 19
T 41 /system/1/assets/files/000/000/961/961/be2680966/original/TF070.wav 554/440 @ 0.65Hz (0.76s / 0.76s) Alternating T 1 T 8 T 19
T 42 /system/1/assets/files/000/000/962/962/314fe8a1b/original/TF071.wav 561/760 @ 0.83Hz (0.60s / 0.60s) Alternating T 1 T 8 T 19
T 43 /system/1/assets/files/000/000/963/963/5f6deb8a1/original/TF072.wav 780/600 @ 0.96Hz (0.52s / 0.52s) Alternating T 1 T 8 T 19
T 44 /system/1/assets/files/000/000/419/419/e353c86c4/original/TF002.WAV 800/1000 @ 2Hz (0.25s / 0.25s) Alternating T 5 T 24 T 19
T 45 /system/1/assets/files/000/000/419/419/e353c86c4/original/TF002.WAV 970/800 @ 2Hz (0.25s / 0.25s) Alternating T 1 T 8 T 19
T 46 /system/1/assets/files/000/000/375/375/771bd7a3e/original/TF012.WAV 800/1000 @ 0.875Hz (0.57s / 0.57s) Alternating T 53 T 24 T 19
T 47 /system/1/assets/files/000/000/374/374/021ee6540/original/TF010.WAV 2400/2900 @ 2Hz (0.25s / 0.25s) Alternating T 57 T 24 T 19
T 48 /system/1/assets/files/000/000/965/965/e3d76c24c/original/TF073.wav 500/1200 @ 0.3Hz (1.67s / 1.67s) Sweeping T 44 T 24 T 12
T 49 /system/1/assets/files/000/000/964/964/4e1cd3f7f/original/TF074.wav 560/1055 @ 0.18Hz (2.73s / 2.73s) Sweeping T 44 T 24 T 12
T 50 /system/1/assets/files/000/000/966/966/a8e5f4440/original/TF075.wav 560/1055 @ 3.3Hz (0.15s / 0.15s) Sweeping T 44 T 24 T 12
T 51 /system/1/assets/files/000/000/969/969/5734194b1/original/TF076.wav 600/1250 @ 0.125Hz (4s / 4s) Sweeping T 44 T 24 T 12
T 52 /system/1/assets/files/000/000/394/394/1bfee2f1b/original/TF031.WAV 660/1200 @ 1Hz (0.50s / 0.50s) Sweeping T 64 T 24 T 12
T 53 /system/1/assets/files/000/000/420/420/50f9ee7a7/original/TF004.WAV 800/1000 @ 1Hz (0.50s / 0.50s) Sweeping T 56 T 24 T 12
T 54 /system/1/assets/files/000/000/392/392/68d5d1294/original/TF029.WAV 800/1000 @ 7Hz (0.07s / 0.07s) Sweeping T 57 T 24 T 12
T 55 /system/1/assets/files/000/000/389/389/68683d240/original/TF024.WAV 800/1000 @ 50Hz (0.01s / 0.01s) Sweeping T 54 T 24 T 12
T 56 /system/1/assets/files/000/000/422/422/42b72dd93/original/TF006.WAV 2400/2900 @ 7Hz (0.07s / 0.07s) Sweeping T 57 T 24 T 12
T 57 /system/1/assets/files/000/000/373/373/a686b0abe/original/TF007.WAV 2400/2900 @ 1Hz (0.50s / 0.50s) Sweeping T 47 T 24 T 12
T 58 /system/1/assets/files/000/000/398/398/7c1bf5e00/original/TF025.WAV 2400/2900 @ 50Hz (0.01s / 0.01s) Sweeping T 54 T 24 T 12
T 59 /system/1/assets/files/000/000/967/967/2e92dbc46/original/TF077.wav 2500/3000 @ 2Hz (0.25s / 0.25s) Sweeping T 44 T 24 T 12
T 60 /system/1/assets/files/000/000/968/968/5dfcb9aea/original/TF078.wav 2500/3000 @ 7.7Hz (0.65s / 0.65s) Sweeping T 44 T 24 T 12
T 61 /system/1/assets/files/000/000/408/408/e0fadcdd2/original/TF042.WAV 800Hz Motor Siren T 44 T 24 T 12
T 62 /system/1/assets/files/000/000/404/404/1c1741943/original/TF041.WAV 1200Hz Motor Siren T 44 T 24 T 12
T 63 /system/1/assets/files/000/000/409/409/590aa5e82/original/TF044.WAV 2400Hz Motor Siren T 44 T 24 T 12
T 64 /system/1/assets/files/000/000/395/395/631e82dc8/original/TF026.WAV Simulated Bell T 44 T 21 T 12
Country specific or custom tone configurations and alarm frequencies are available upon request.

Upcoming Events

Fse (4)
Cafaa%202020%20final%20cmyk
Logo
Nfpa conference expo