Alarm Horn: | |
Maximum output: | High power level: 114dB(A) @ 1 m +/- 3dB [105dB(A) @ 10ft/3m +/- 3dB] Default power level: 112dB(A) @ 1 m +/- 3dB [103dB(A) @ 10ft/3m +/- 3dB] |
Nominal output: | High power level: 109dB(A) @ 1m +/- 3dB [100dB(A) @ 10ft/3m] +/- 3dB Default power level: 107dB(A) @ 1m +/- 3dB [98dB(A) @ 10ft/3m] +/- 3dB |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Full range |
Effective range: | 125m/410ft @ 1KHz |
Voltages DC: | 24Vdc (20-28Vdc) |
Voltages AC: | 110-120Vac, 220-240Vac |
Stage switching: | DC units: negative or positive AC units: common supply line |
Strobe Beacon: | |
Energy: | 10 Joules (10Ws) |
Flash rates: | Option 1: 1Hz (60 fpm) Option 2: 1.5Hz (90 fpm) Option 3: Double Strike |
Peak Candela: | 1,000,000 cd – calculated from energy (J) |
Effective Intensity: | 500 cd – calculated from energy (J) |
Peak Candela: | 85,544 cd* – measured ref. to I.E.S. |
Effective Intensity: | 260 cd* – measured ref. to I.E.S. |
Lens colours: | Amber, Blue, Clear, Green, Magenta, Red & Yellow |
Tube life : | Emissions reduced to 70% > 5 million flashes |
General: | |
Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
Ingress protection: | EN60529: IP66/67 UL50E / NEMA250: 4 / 4X / 3R / 13 |
Enclosure material: | Marine grade aluminium LM6 – copper free Chromated & powder coated – corrosion proof |
Enclosure colour: | Red or Grey, custom colours available on request |
Cable entries: | 1×1/2"NPT & 2xM20 – thread adaptors available |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) Pluggable, duplicated terminals |
Grounding stud: | M5 |
Line monitoring: | Blocking diode included. EOL Min. 500 Ohm 2W, or 3k3 Ohm 0.5W resistor or diode (DC versions) can be fitted |
Enclosure volume: | <2 litres |
Installation temp: | -55 to +85°C [-67° to +185°F] |
Storage temp: | -55 to +85°C [-67° to +185°F] |
Relative humidity: | 99% |
Vibration test: | 35Hz for a duration 4Hr (UL464) |
Jarring test: | 3ft/lb Energy (UL464) |
Impact test: | 3x 5lb (UL464) |
Relative humidity: | 95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
Weight: | 5.0kg/10.10lbs |
Voltage range: |
Nominal Voltage: |
Xenon Strobe Nominal current: |
Alarm Horn Default Power Nominal current: |
Alarm Horn High Power Nominal current: |
Combined Default Power Nominal current: |
Combined High Power Nominal current: |
Combined Default Power Maximum current: |
Combined High Power Maximum current: |
In Rush |
---|---|---|---|---|---|---|---|---|---|
20-28Vdc | 24Vdc | 673mA | 324mA | 740mA | 997mA | 1413mA | 1091mA | 1507mA | 786mA <5ms |
110-120Vac 50/60Hz |
115Vac | 247mA | 125mA | 285mA | 372mA | 532mA | 449mA | 636mA | |
220-240Vac 50/60Hz |
230Vac | 121mA | 78mA | 167mA | 199mA | 288mA | 199mA | 362mA |
Part Code: | Identifier: | Description: |
---|---|---|
Product type: | D1xC2X10 | Combined Alarm Horn & Xenon Strobe |
Horn type: | R | Omni-directional radial horn |
Voltage: | DC024 AC115 AC230 |
20-28V dc 110-120Vac 220-240Vac |
Cable entries:[e] | A B C D F G Note: |
2 x M20x1.5mm & 1 × 1/2"NPT 2 × 1/2"NPT – adaptors 2 × 3/4"NPT – adaptors 2 x M25x1.5mm – adaptors 1 × 3/4"NPT – adaptor 1 x M25x1.5mm – adaptor All entries, excluding thread adaptors, supplied with stopping plugs installed. |
Stopping plug/ adaptor material: [m] |
B N S |
Brass Nickel Plated Stainless Steel |
Bracket/Guard material: [s] | 1 3 5 6 7 8 |
U bracket A4 316 Stainless Steel U bracket A4 316 St/St with Equip. Tag U bracket A4 316 St/St with Equip. Tag & Duty Label Surface bracket A4 316 SS Surface bracket A4 316 SS with Equip. Tag Surface bracket A4 316 SS with Equip. Tag & Duty Label |
Product version: [v] |
A | UL, cUL, ULC, IECEx, ATEX, CSFM, INMETRO – SIL1 & SIL2 |
Product option: [o] |
1 Z X Y |
Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 or 8 |
Enclosure colour: [x] | G R S |
Grey Red Special colour – contact E2S |
Lens colour: [y] | A B C G M R Y |
Amber Blue Clear Green Magenta Red Yellow |
Accessories: | ||
SP65-0001-A4 SP65-0003-A4 |
Pole Mount Bracket Kit St/St A4 (316) Sunshade – St/St A4 (316) |
|
Stage control: | ||
Please review the installation manual and wiring schematics for remote stage control and EOL resistor monitoring configuration options: | ||
Config. 1 or 5 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 2 or 6 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 3 or 7 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | |
Config. 4 or 8 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | |
Config. 1 or 2 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts |
Amber | Blue | Clear | Green | Magenta | Red | Yellow |
0.59 | 0.27 | 1.00 | 0.51 | 0.34 | 0.15 | 0.85 |