Alarm Horn: | |
---|---|
Maximum output: | 113dB(A) @ 1 m +/- 3dB [107dB(A) @ 10ft/3m +/- 3dB] |
Nominal output: | 108dB(A) @ 1m +/- 3dB [104dB(A) @ 10ft/3m] +/- 3dB |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Full range |
Effective range: | 125m/410ft @ 1KHz |
Voltages DC: | 12Vdc (11.5-14Vdc), 24Vdc (20-28Vdc), 48Vdc (42-54Vdc |
Voltages AC: | 230vac (220-240vac) |
Stage switching: | DC units: negative or positive AC units: common supply line |
Strobe Beacon: | |
Energy: | 5 Joules (5Ws) |
Flash rates: | 1Hz flash (60 fpm) 1.5Hz flash (90 fpm) Double flash (120 fpm) |
Eff. Intensity: | 143 cd* – measured ref. to I.E.S. |
Peak Candela: | 46,976 cd* – measured ref. to I.E.S. |
Eff. Intensity: | 250 cd – calculated from energy (J) |
Peak Candela: | 500,000 cd – calculated from energy (J) |
Lens colours: | Amber, Blue, Clear, Green, Magenta, Red & Yellow |
Tube life : | Emissions are reduced to 70% after 5 million flashes |
General: | |
Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
Ingress protection: | EN60529: IP66 |
Enclosure material: | 316L Stainless Steel |
Enclosure colour: | Red |
Enclosure finish: | Chromate & powder coated finish |
Cable entries: | 3 x M20x1.5mm Stopping plugs included |
Stopping plugs: | Stainless Steel |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) Pluggable & duplicated terminals |
Line monitoring: | Diode polarized for use in supervised circuits Blocking diode for reverse polarity monitoring |
Ground/Earth stud: | M5 |
Line monitoring: | Blocking diode included EOL Min. 500 Ohm 2W, or 3k3 Ohm 0.5W resistor or diode (DC versions) can be fitted |
Enclosure volume: | <2 litres |
Installation temp: | -50° to +70°C (-58°F to +158°F) |
Storage temp: | -50° to +70°C (-58°F to +158°F) |
Relative humidity: | 95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
Weight: | 7.2kg/15.87lbs |
Nominal Voltage: |
Voltage range: |
Alarm Horn Nominal current: |
Xenon Strobe Nominal current: |
Combined Nominal current: |
Combined Max. current: |
In Rush |
---|---|---|---|---|---|---|
12Vdc | 11.5-14Vdc | 221mA | 678mA | 885mA | 920mA | |
24Vdc | 20-28Vdc | 185mA | 323mA | 508mA | 555mA | 786mA <5us |
48Vdc | 42-54Vdc | 115mA | 198mA | 325mA | 420mA | |
230Vac | 220-240Vac 50/60Hz |
48mA | 79mA | 127mA | 149mA |
Part Code: | Identifier: | Description: |
---|---|---|
Product type: | STExC1X05 | STExC1 Combined Alarm |
Horn type: | R | Radial – omnidirectional horn |
Voltage: | DC012 DC024 DC048 AC230 |
11.5-14Vdc 20-284Vdc 42-54Vdc 220-240Vac |
Cable entries:[e] | A B C D E F G |
3 x M20x1.5mm 2 × 1/2" NPT – adaptors 2 × 3/4" NPT – adaptors 2 x M25x1.5mm – adaptors 1 × 1/2" NPT – adaptor 1 × 3/4" NPT – adaptor 1 x M25x1.5mm – adaptor |
Stopping plug/ adaptor material: [m] |
B N S |
Brass Nickel Plated Stainless Steel (standard) |
Bracket / Guard material: [s] | 1 3 |
A4 316 Stainless Steel A4 316 St/St with Equip. Tag |
Product version: [v] | A | UL, cUL, IECEx, ATEX, Ex EAC, INMETRO – SIL1 & SIL2 Note: UL, cUL approval not applicable to 12Vdc or 115Vac variants |
Product option: [o] |
1 Z X Y |
Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 or 8 |
Enclosure colour: [x] | G R S |
Grey Red Special colour – contact E2S |
Lens colour: [y] | A B C G M R Y |
Amber Blue Clear Green Magenta Red Yellow |
Accessories: | ||
SP65-0001-A4 SP65-0003-A4 |
Pole Mount Bracket Kit St/St A4 (316) Sunshade – St/St A4 (316) |
|
Alarm stage control: | ||
Please review the installation manual and wiring schematics for remote stage control and EOL resistor monitoring configuration options: | ||
Config. 1 or 5 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 2 or 6 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 3 or 7 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | |
Config. 4 or 8 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | |
Config. 1 or 2 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts |
Amber | Blue | Clear | Green | Magenta | Red | Yellow |
0.59 | 0.27 | 1.00 | 0.51 | 0.34 | 0.15 | 0.85 |