Maximum output: | High power level: 124dB(A) @ 1 m ±3dB [115dB(A) @ 10ft/3m ±3dB] Default power level: 121dB(A) @ 1 m ±3dB [112dB(A) @ 10ft/3m ±3dB] |
Nominal output: | High power level: 121dB(A) @ 1m ±3dB [112dB(A) @ 10ft/3m] ±3dB Default power level: 118dB(A) @ 1m ±3dB [109dB(A) @ 10ft/3m ±3dB] |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Full range to 0dB(A) |
Effective range: | High power level: 323m/1062ft @ 1KHz Default power level: 221m/726ft @ 1KHz |
Voltages DC: | 11.5-54V dc |
Voltages AC: | 100-240V ac 50/60Hz |
In rush: | 815mA within 4.0ms @ 24Vdc |
Stage switching: | Negative, positive, voltage free |
Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
Ingress protection: | IP66 Type 4/4X/13/3R |
Enclosure: | High impact UL94 V0 & 5VA FR ABS |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
Line monitoring: | Diode polarized for use in supervised circuits |
Operating: | -40 to +66°C [-40° to +151°F] |
Storage: | -40 to +70°C [-40° to +158°F] |
Relative humidity: | 99% |
Vibration test: | 35Hz for a duration 4Hr (UL464) |
Jarring test: | 3ft/lb Energy (UL464) |
Impact test: | 3x 5lb (UL464) |
MTBF DC: | 93.92 years / 822,706 hours – MIL 217 |
MTBF AC: | 46.66 years / 408,508 hours – MIL 217 |
Weight DC: | 2.10kg / 4.62lbs |
Weight AC: | 2.70kg / 5.94lbs |
Product Version: | Nominal Voltage: | Voltage Range: | Default Power Level Current: |
High Power Level Current: |
---|---|---|---|---|
DC024 | 12dc 24Vdc 48Vdc |
11.5-54Vdc | 376mA 430mA 223mA |
440mA 930mA 453mA |
AC230 | 115Vac 50/60Hz 230Vac 50/60Hz |
100-240Vac | 173mA 105mA |
340mA 212mA |
Variable: | Identifier: | Description: |
---|---|---|
Product type: | A121 | Alarm horn sounder |
Voltage: | DC024 AC230 |
11.5-54Vdc 100-240Vac 50/60Hz |
Back box/cable entries: [e] | A | Back box with mounting lugs – 2 x M20, 1/2"NPT clearance entries |
Stopping plug material: [m] | A | ABS |
Equip. tag/Duty label: [s] | 0 1 2 |
No equip. tag or Duty label 316 (A4) St/St Equip. tag/Duty label Metalised Polyester Equip. tag/Duty label |
Product version: [v] |
A | UL/cUL, ULC, CPR, MED, DNV, USCG, RMRS, EAC, CE, UKCA – SIL1 & SIL2 |
Product option: [o] |
1 Z X Y K |
Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 Stage control Config. 5 (DC) and Config. 2 (AC) |
Enclosure colour: [x] | G R S |
Grey Red Special colour – contact E2S |
Alarm stage control: | ||
Please review the installation manual and wiring schematics for remote stage control and EOL resistor monitoring configuration options: | ||
Config. 1 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 2 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 3 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | |
Config. 4 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | |
Config. 5 [DC]: | Product option ‘K’. Horn continuously powered. Voltage free activation of up to 3 alarm stages | |
Config. 1 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts | |
Config. 2 [AC]: | Product option ‘K’. Horn continuously powered. Voltage free activation of up to 3 alarm stages |