Alarm Horn: | |
---|---|
Maximum output: | 110dB(A) @ 1 m ±3dB [101dB(A) @ 10ft/3m ±3dB] |
Nominal output: | 102dB(A) @ 1m ±3dB [93dB(A) @ 10ft/3m ±3dB] |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | -12dB(A) tone dependent |
Effective range: | 38m/124ft @ 1KHz |
In rush: | 636mA within 4.0ms @ 24Vdc |
Stage switching: | Negative (common positive) |
Xenon Strobe: | |
Energy: | 5 Joules(5Ws) |
Flash rate: | 1Hz (60 fpm) DC units: 1.5Hz (90 fpm) & Double strike |
Peak Candela: | 500,000 cd – calculated from energy (J) |
Effective cd: | 250 cd – calculated from energy (J) |
Peak Candela: | 86,935 cd* – measured ref. to I.E.S. |
Effective cd: | 200 cd* – measured ref. to I.E.S. |
Tube life: | Emissions may reduce to 70% after 8 million flashes |
General: | |
Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
Ingress protection: | IP66 Type 3R/13 |
Enclosure: | High impact UL94 V0 & 5VA FR ABS/PC |
Lens colour filter: | Field replaceable UV stable PC |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
Line monitoring: | Diode polarized for use in supervised circuits |
Operating: | -40 to +66°C [-40° to +151°F] |
Storage: | -40 to +70°C [-40° to +158°F] |
Relative humidity: | 95% at 20°C [68°F] |
Vibration test: | 35Hz for a duration 4Hr (UL464/UL1638) |
Jarring test: | 3ft/lb Energy (UL464/UL1638) |
Impact test: | 3x 5lb (UL464/UL1638) |
MTBF DC: | 114.79 years / 1,005,530 hours – MIL 217 |
MTBF AC: | 86.29 years / 755,857 hours – MIL 217 |
Weight DC: | 0.46kg / 1.01lbs |
Weight AC: | 0.57kg / 1.25lbs |
Product Version: | Nominal Voltage: | Voltage Range: | Beacon Current: | Horn Current: | In Rush |
---|---|---|---|---|---|
DC012 | 12Vdc | 11.5-14Vdc | 341mA | 17mA | |
DC024 | 24Vdc | 20-28Vdc | 250mA | 33.5mA | 853mA <2.2ms |
DC048 | 48Vdc | 42-54Vdc | 170mA | 113mA | |
AC024 | 24Vac | 24-28Vac 50/60Hz | 300mA | 42.5mA | |
AC048 | 48Vac | ±10% 50/60Hz | 250mA | 42.5mA | |
AC115 | 115Vac | ±10% 50/60Hz | 70mA | 25mA | |
AC230 | 230Vac | ±10% 50/60Hz | 35mA | 17mA |
Variable: | Identifier: | Description: |
---|---|---|
Product type: | AL100X | Combined alarm horn sounder & Xenon strobe |
Voltage: | DC012 DC024 DC048 AC024 AC048 AC115 AC230 |
12Vdc (11.5-14Vdc) 24Vdc (20-28Vdc) 48Vdc (42-54Vdc) 24Vac 50/60Hz 48Vac 50/60Hz 115Vac 50/60Hz 230Vac 50/60Hz |
Back box/cable entries: [e] | M | Back box with mounting lugs – 2 x M20, 1/2"NPT clearance |
Stopping plug material: [m] | A | ABS |
Equip. tag/Duty label: [s] | 0 1 2 |
No equip. tag or Duty label 316 (A4) St/St Equip. tag/Duty label Metalised Polyester Equip. tag/Duty label |
Product version: [v] |
A | UL/cUL, CPR, RMRS, EAC, CE, UKCA – SIL1 & SIL2 |
Product option: [o] |
1 X Z |
Standard product Custom configuration – contact E2S Custom alarm tone software – contact E2S |
Enclosure: [x] | R G W |
Red Grey White |
Lens colour: [y] | A B C G M R Y |
Amber Blue Clear Green Magenta Red Yellow |