Datasheet | Datasheet.pdf |
Installation Manual | D221-01-351-IS_Issue_8__AL121H_.pdf |
UL certificate of compliance | UL_CoC_-_20210430-S7995_ALERTALARM.pdf |
Russian EAC Declaration of Conformity | D-GB.G05..12595-20-24.03.2025.pdf |
CSFM Listing | CSFM_Listing_2279-0513_A-Series_2025.pdf |
Russian Fire certificate | EAC_Certificate_043_TR_CU-.00291.pdf |
Russian Maritime register | 19.00193.278.pdf |
UAE Civil Defence | UAE_Civil_Defence_CoC_ULSZ_UVAV.S7995.pdf |
Declaration of Conformity | DC-084_Issue_A_AlertAlight.pdf |
Declaration of Conformity UKCA | DC-086_Issue_A_UKCA_AlertAlight.pdf |
SIL Certificate: Product version [A] | T1072-215-2_SIL2_SIL1_2H__D1xS_D1xC_STExS_STExC_GNExS_A112N_AL112N_A121_AL121_MA_.pdf |
2D drawing (PDF) | D221-05-251_Issue_A.pdf |
2D drawing (DWG) | D221-05-251_Issue_A.DWG |
3D drawing (STEP) | D221-05-251-3D_Issue_A.STEP |
Wiring Schematic DC voltage | D221-06-251_Issue_B.pdf |
Wiring Schematic AC voltage | D221-06-255_Issue_A.pdf |
Alarm Horn: | |
---|---|
Maximum output: | High power level: 124dB(A) @ 1m ±3dB [115dB(A) @ 10ft/3m ±3dB] Default power level: 121dB(A) @ 1 m ±3dB [112dB(A) @ 10ft/3m ±3dB] |
Nominal output: | High power level: 121dB(A) @ 1m ±3dB [112dB(A) @ 10ft/3m ±3dB] Default power level: 118dB(A) @ 1m ±3dB [109dB(A) @ 10ft/3m ±3dB] |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Full range to 0dB(A) |
Effective range: | High power level: 323m/1062ft @ 1KHz Default power level: 221m/726ft @ 1KHz |
In rush: | 815mA within 4.0ms @ 24Vdc |
Stage switching: | Negative (common positive) |
L.E.D Beacon: | |
Light source: | High intensity L.E.D. array. 18 x Cree© SMT White LED |
High Power Steady: | 180 cd – measured ref. to I.E.S. |
1Hz Flash cd: | 113 cd – measured ref. to I.E.S. |
LED life: | 60,000 hours |
Settings: | 1. High Power Steady 2. Blinking – 425ms ON 75ms OFF 3. 1.0Hz (60 fpm) – 200ms ON 800ms OFF 4. 1.33Hz (80fpm) – 150ms ON 600ms OFF 5. Double Flash 6. Triple Flash 7. 2.0Hz (120fpm) – 125ms ON 375ms OFF 8. Temporal Pattern Flash |
General: | |
Safety Integrity Level: | SIL1 and SIL2 Route 2H IEC61508 (2010) |
Ingress protection: | IP66 Type 4/4X/13/3R |
Enclosure: | High impact UL94 V0 & 5VA FR ABS/PC |
Lens colour filter: | Field replaceable UV stable PC |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
Line monitoring: | Diode polarized for use in supervised circuits |
Operating: | -40 to +66°C [-40° to +151°F] |
Storage: | -40 to +70°C [-40° to +158°F] |
Relative humidity: | 95% at 20°C [68°F] |
Vibration test: | 35Hz for a duration 4Hr (UL464/UL1638) |
Jarring test: | 3ft/lb Energy (UL464/UL1638) |
Impact test: | 3x 5lb (UL464/UL1638) |
MTBF DC: | 66.52 years / 582,750 hours – MIL 217 |
MTBF AC: | 36.35 years / 318,420 hours – MIL 217 |
Weight DC: | 2.30kg / 5.06Ibs |
Weight AC: | 2.90kg / 6.39Ibs |
Product Version: | Nominal Voltage: | Voltage Range: | Beacon Current: | Horn Default Power Level Current: |
Horn High Power Level Current: |
---|---|---|---|---|---|
DC024 | 12Vdc | 11.5-14Vdc | 79.5mA | 376mA | 440mA |
DC024 | 24Vdc | 16-33Vdc (Regulated) |
87mA | 430mA | 930mA |
DC048 | 48Vdc | 48-54Vdc | 60mA | 233mA | 453mA |
AC230 | 115Vac 230Vac |
100-240 Vac 50/60Hz | 34mA 19mA |
173mA 340mA |
105mA 212mA |
Variable: | Identifier: | Description: |
---|---|---|
Product type: | AL121H | Combined alarm horn sounder & LED beacon |
Voltage: | DC024 DC048 AC230 |
12Vdc (11.5-14Vdc)/24Vdc (20-28Vdc) 48Vdc (48-54Vdc) 100-240 Vac 50/60Hz |
Back box/cable entries: [e] | A | Back box with mounting lugs – 2 x M20, 1/2"NPT clearance |
Stopping plug material: [m] | A | ABS |
Equip. tag/Duty label: [s] | 0 1 2 |
No equip. tag or Duty label 316 (A4) St/St Equip. tag/Duty label Metalised Polyester Equip. tag/Duty label |
Product version: [v] |
A | UL/cUL, ULC, RMRS, EAC, CE, UKCA – SIL1 & SIL2 |
Product option: [o] |
1 Z X Y |
Standard product Custom alarm tone software – contact E2S Custom configuration – contact E2S Stage control Config. 4 or 8 |
Enclosure colour: [x] | G R S |
Grey Red Special colour – contact E2S |
Lens colour: [y] | A B C G M R Y |
Amber Blue Clear Green Magenta Red Yellow |
Alarm stage control: | ||
Please review the installation manual and wiring schematics for remote stage control and EOL resistor monitoring configuration options: | ||
Config. 1 or 5 [DC]: | Factory default. Common negative, positive switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 2 or 6 [DC]: | User setting. Common positive, negative switching. Up to 4 Alarm Stages. EOL monitoring Alarm Stage 1 only | |
Config. 3 or 7 [DC]: | User setting. Common negative, positive switching activation of Alarm Stages 1 & 2 with EOL on both stages. Reverse polarity monitoring | |
Config. 4 or 8 [DC]: | Product option ‘Y’. Independent activation of Alarm Stages 1 & 2 with EOL on both stages. Forward polarity monitoring | |
Config. 1 or 2 [AC]: | Factory default. Up to 4 Alarm Stages. Stage 1 activated at power on. Stages 2, 3 and 4 via volt free contacts |