Electrical equipment for flammable gases and dust | |||||||||||||||
Symbol | Type of protection | Basic concept of protection | Suitable for Zones |
Typical EPL |
EN / IEC Standard | ||||||||||
0 | 1 | 2 | 20 | 21 | 22 | Ga | Gb | Gc | Da | Db | Dc | ||||
e | Increased safety | No arcs, sparks or hot surfaces, enclosure IP54 or better | • | • | • | 60079-7 | |||||||||
n | Type ‘n’ (non-sparking) | • | • | 60079-15 | |||||||||||
Type ‘n’ (closed-break) | Containment of the explosion | • |
• |
||||||||||||
Type ‘n’ (sealed and hermetically sealed) | Keep the flammable substances out | • |
• |
||||||||||||
Type ‘n’ (restriced breathing) | • |
• |
|||||||||||||
d | Flameproof | Containment of the explosion | • |
• |
• |
60079-1 | |||||||||
q | Powder filled | Quenching of the flame | • |
• |
• |
60079-5 | |||||||||
ia | Intrinsic safety | Limitation of spark energy and surface temperatures | • |
• |
• |
• |
• |
• |
• |
• |
60079-11 | ||||
ib | • |
• |
• |
• |
• |
• |
|||||||||
ic | • |
• |
• |
• |
|||||||||||
px | Pressurised enclosure | Keep the flammable substances out | • |
• |
• |
60079-2 | |||||||||
py | • |
• |
• |
||||||||||||
pz | • |
• |
|||||||||||||
ma | Encapsulation | • |
• |
• |
• |
• |
• |
• |
• |
60079-18 | |||||
mb | • |
• |
• |
• |
• |
• |
|||||||||
mc | • |
• |
• |
||||||||||||
o | Oil immersion | • |
• |
• |
60079-6 | ||||||||||
Op pr | Optical radiation | Inherently safe, protected by shutdown | • |
• |
• |
60079-28 | |||||||||
Op sh | • |
• |
• |
• |
|||||||||||
Op is | • |
• |
• |
• |
|||||||||||
ta | Dust ignition protection by enclosure | Dust-tight enclosure | • |
• |
• |
• |
60079-31 | ||||||||
tb | • |
• |
• |
||||||||||||
tc | • |
• |
|||||||||||||
pd | Pressurised enclosure | Keep the flammable substances out | • |
• |
• |
61241-4 | |||||||||
• |
• |